| Standard |
EN 50155, GB/T 24338.4-2018, EN 45545-2, IEC 61373 |
| Adaption |
Acti9 Series 1P-4 |
| Electrical Characteristics |
|
| Operating Voltage |
230V AC(70%~125%) 24-48V DC(optional) |
| Control signal |
MODBUS-RS485 Wet node 230V high level/pulse signal (optional) |
| Over&Under voltage function |
160-275V ±5V (optional) |
| Timing function |
Available (optional) |
| Digital display |
3-digit voltage, switching times, fault status |
| Effective control signal duration |
>400ms |
| Closing action time |
< 1s |
| Opening action time |
< 0.5s |
| Control circuit cable length |
≤1500m |
| Current-carrying capacity of auxiliary contacts (terminals 8-9-10) |
1CO, minimum operating current 3mA (24VDC) (resistive) (optional) |
| Current-carrying capacity of signaling contacts (terminals 5-6-7) |
Maximum operating current 2A (30V DC), 0.5A (125V AC) (optional) |
| Power consumption |
≤ 1.5VA (static); ≤25VA (dynamic) |
| Rated insulation voltage |
400V |
| Rated Impulse Withstand Voltage Uimp |
|
| (between S2C-RM DC and MCB) |
4kV (4.9kV at sea level) |
| Self-locking protection |
Within 10s of 3CO / 20s of 4CO / 30s of 6CO, the product will
self-lock and recover automatically after 40s. |
| Electrical life |
10000 times, 3 times/minute |
| Mechanical Characteristics |
|
| Indicator Light |
Green, Normal status |
|
Red, MCB overcurrent fault |
| Auto/Manual switching |
Auto Remote control of opening&closing available |
|
Manual Remote control of opening&closing disabled |
| Mechanical life |
10000 |
| Protection class |
Ip20 |
| Hazard class according to EN 45545-2 |
EN 45545-2 R26 /HL3 |
| Shock and vibration resistance According to IEC 61373 |
category 1 – class A/B – body mounted |
| Resistance to heat and humidity IEC/EN 60068-2-30 |
28 cycles (55°C/90-96 % , 25°C/95-100 %) |
| Ambient Temperature |
-25…+70℃ |
| Storage Temperature |
-40…+70℃ |
| Installation and Wiring |
|
| Power and control signal terminal wiring capacity |
28-12AWG 2.5mm² |
| Auxiliary signal terminal wiring capacity |
28-14AWG 1.5mm² |
| DIN rail mounting |
DIN rail EN 60715 (35 mm) |
| Mounting position |
Mounting on DIN rail Any position |