| Technical parameters |
| General instructions |
| Output type |
NPN、PNP、D、AD |
| Installation method |
Flush mounting |
| Rated operating distance Sn |
15mm |
| Raliable operating range distance Sa |
0…12mm |
| Standard detection target |
45*45*1t(Q253A) |
| Rated grade |
| Rated voltage UB |
NPN/PNP/D:DC:10..30VDC,AD:AC/DC:24-250V |
| Switch frequency f |
NPN/PNP/D:0.25KHz,AD:40Hz |
| Hysteresis range |
1-15%of detection distance |
| Repeatability |
<3%of detection distance |
| No-load current lo |
<15mA |
| Leakage current Ir |
<100uA |
| Voltage drop Ud |
NPN/PNP/D:<2.5V,D:<3.5V,AD:<10V |
| Working current IL |
NPN/PNP:<200mA,D:<100mA,AD:<300mA |
| Circuit protection |
Reverse polarity protection,output short circuit protection,surge absorption |
| Switch status indication |
Red LED indicator |
| Surroundings |
| Ambient temperature |
-25℃…70℃(248…358K) |
| Temperature effect |
-25℃…70℃,detection distance within 10%at+24℃ |
| Environment humidity |
35…95%RH |
| Voltage influence |
<3% |
| Mechanical characteristics |
| Wiring form |
Standard wire length 2m |
| Case material |
Brass nickel plating |
| Inductive surface |
PBT |
| Protection level |
IP66 |
| High voltage resistance |
1000VAC,50/60Hz for 1 minute between charged parts and the case |
| Insulation resistance |
50MΩ or more(DC500V)for the charged parts and case |
| Vibration resistance |
10~55 Hz,amplitude 1.5mm X,Y,Z each direction 2H |
| Certifications and Standards |
| Product cetificates |
CE CCC CQC ISO9001 |
| Standards compliant |
IEC/EN 60947-5-2:2004 |